Willseal | UL Classified Fire Rated Systems
Head of Wall
**Click on the UL listing name for further information in a PDF format**
UL Listing Sealant Name |
Fire Rating (Hours) |
Nominal Joint Width (inches) |
Foam Depth (inches) |
Movement | Substrate | |
---|---|---|---|---|---|---|
Min | Max | |||||
HW-D-0700 – conf. A FR joint, FR joint UC |
3 | 1/2 in. | 1-7/8 in. | 3 or 4 in. | ± 50% | Concrete |
HW-D-0700 – conf. B FR joint UC |
3 | 1/2 in. | 1-7/8 in. | 3 or 4 in. (4 in. foam required for 3 hour rating) |
± 50% | Concrete |
HW-D-1101 – conf. A FR joint, FR joint UC |
3 | 2 in. | 3-3/8 in. | 4 in. | ± 50% (2 in. to 3 in.) + 25% / – 50% (2 in. to 3-3/8 in.) |
Concrete |
HW-D-1101 – conf. B FR joint UC |
3 | 2 in. | 3-3/8 in. | 3 or 4 in. | ± 50% (2 in. to 3 in.) + 25% / – 50% (2 in. to 3-3/8 in.) |
Concrete |
Reprinted from the Online Certifications Directory with permission from UL
© 2013 UL LLC